| 요약1 |
본 연구에서는 의료환경에서의 공기매개 감염 저감을 위한 국부배기(Local Exhaust Ventilation, LEV) 시스템의 성능 향상을 목표로, 후드 형상 최적화에 따른 유동 특성 및 에어로졸 포집 성능을 CFD 수치해석과 면풍속 측정, rlfb 가시화 및 PIV 실험을 통해 종합적으로 분석하였다. 기존 산업 환기용 반구형 후드(ALT-1)와 유선형 구조의 개선된 후드(ALT-2)를 대상으로 동일 조건에서 비교 평가를 수행하였다. |
| 요약2 |
This study investigates the effect of hood shape optimization on the airflow characteristics and aerosol capture performance of a local exhaust ventilation (LEV) system for infection control in healthcare environments. To evaluate the performance improvement, a baseline hemispherical hood (ALT-1, Type 09) and an optimized streamlined hood (ALT-2, Type 12) were designed and compared under identical operating conditions. A combined approach using computational fluid dynamics (CFD), face velocity measurements, flow visualization, and particle image velocimetry (PIV) was applied to analyze airflow and capture behavior. The CFD results showed that the optimized hood effectively induces converging airflow toward the exhaust center while reducing recirculation zones. Experimental results demonstrated that the optimized hood increased the average face velocity by approximately 3.5% and improved airflow uniformity. Flow visualization confirmed that aerosol dispersion toward healthcare workers was reduced under various breathing directions, while PIV analysis showed increased mean velocity (approximately 25%) and reduced low-velocity regions. Overall, the optimized hood improved airflow stability and aerosol capture performance by modifying the flow structure rather than simply increasing airflow rate. These findings provide a practical design strategy for enhancing LEV performance in healthcare settings and reducing airborne infection risk. |