| 논문명 |
데이터센터 IT장비 냉각유체 공급온도에 따른 수냉식 냉각 시스템 구성 및 에너지 효율 기준에 대한 연구 / Evaluating the Effects of Coolant Supply Temperature on Liquid Cooling System Design and Efficiency in Data Centers |
| 수록사항 |
대한건축학회논문집, Vol.41 No.9 (2025-09) |
| 주제어 |
데이터센터; 수냉식 시스템; IT장비냉각설비; 냉각유체 공급온도; 에너지효율지표 ; Data Center; Liquid Cooling System; Technology Cooling System; Coolant Supply Temperature; Power Usage Effectiveness |
| 요약1 |
본 연구는 수냉식 냉각시스템의 구성과 성능을 냉각유체 공급온도 기준을 중심으로 40개의 조합으로 매트릭스 분석하고, 냉각유체의 물성, 펌프 및 열원장비의 정격전력, 그리고 결과적으로 산출되는 PUEcooling 간의 정량적 상관관계를 평가하였다. 또한 2차측 TCS 냉각유체의 공급온도 조건에 따른 1차측 FWS/CWS 수냉식 시스템의 구성과 각 조건별 기준으로 데이터센터의 냉각 에너지를 분석한 최초의 연구이다. |
| 요약2 |
With the increasing demand for high-density, high-power IT equipment, data center cooling systems must provide both high energy efficiency and effective thermal management. In this context, liquid cooling methods, particularly cold plate and immersion cooling, are drawing attention due to their excellent heat transfer capabilities and suitability for higher coolant supply temperatures. This study presents a matrix-based analysis of 40 system configurations, assessing the energy performance of liquid cooling systems based on coolant supply temperature (S-class), coolant characteristics, rated power of pumps and cooling equipment, and overall system design. Findings indicate that the S-class standard, originally developed for cold plate cooling, can also be applied to immersion cooling systems. Several dielectric fluids maintained stable thermal performance at supply temperatures between 40°C and 50°C. As S-class levels rise, conventional chillers are gradually replaced by cooling towers or dry coolers, cutting the rated power of the FWS/CWS system by up to 75 percent. Pump energy consumption is largely affected by the coolant’s density and thermal properties. Low-viscosity, high-conductivity fluids significantly reduce energy use. Under a 30 MW IT load, systems with higher S-class configurations achieved a design cooling PUE below 1.04. These results underscore the importance of temperature set-points, coolant selection, and system architecture in improving cooling efficiency from the initial planning phase. |