| 논문명 |
이동형 음압격리병실의 환기 시스템 성능 검증을 위한 실험적 연구 / Performance Evaluation of a Mobile Negative Pressure Isolation Room Ventilation System |
| 수록사항 |
대한건축학회논문집, Vol.41 No.8 (2025-08) |
| 주제어 |
이동형 음압격리병실; 환기성능; 오염물 제거효율; 치환기류 ; Mobile Negative Pressure Isolation Room; Ventilation Performance; Contaminant Removal Effectiveness; Displacement Airflow |
| 요약1 |
본 연구의 목적은 선행연구에서 개발된 이동형 음압격리병실의 환기 시스템 성능을 실험적으로 평가하는 것이다. 이를 통해 감염병 대응을 위한 대체 의료 환경의 효율성 및 안전성을 검증하고, 감염원 확산 방지 대책의 기초자료를 제공하는 것을 목표로 한다. 특히, COVID-19와 같은 대유행 시기 동안 의료 시설 내 감염병 확산 방지를 위한 운영 모델을 검토하고, 의료진이 감염원 전파의 매개체가 되는 위험성을 최소화하기 위한 환기 시스템의 설계 및 운영 기준을 제안하였다. |
| 요약2 |
This study evaluates the ventilation performance of a mobile negative pressure isolation room using tracer gas experiments. The goal was to assess its ability to maintain pressure differences, direct airflow from clean to contaminated zones, and remove pollutants efficiently. A calculated CRE value of 1.667 confirmed that contaminant concentrations at the exhaust grilles were approximately 1.67 times higher than in the occupant zone, indicating effective extraction of pollutants from the patient area. Although measured airflow rates varied slightly from design specifications, the system achieved at least 12 ACH, providing adequate dilution and exhaust of airborne contaminants. Sensors located near the exhaust grilles, SP1 and SP2, recorded higher concentrations at 124.38 ppm and 114.11 ppm, respectively. In contrast, sensors positioned farther away, SP3, SP4, and SP5, showed progressively lower levels, measuring 91.11 ppm, 84.29 ppm, and 39.13 ppm. These results confirm the establishment of effective displacement airflow. Meanwhile, the anteroom sensor SP6 registered 0 ppm, indicating that the room’s negative pressure successfully prevented the spread of contaminants to adjacent spaces. These results demonstrate the system’s effectiveness in controlling airborne pollutants, making it a viable option for rapid deployment in pandemic and other emergency healthcare settings. Further studies are recommended to refine airflow distribution and optimize performance through advanced numerical simulations and extended field testing under varied conditions. |