BEMS µ¥ÀÌÅ͸¦ Ȱ¿ëÇÑ µµ¼°ü °Ç¹°ÀÇ ¿îÀüÇöȲ ºÐ¼® / An Operation Status Analysis of Library Building using BEMS Data - Energy Performance Evaluation on Initial Stage of Completion / Áذø Ãʱâ´Ü°èÀÇ °Ç¹° ¿¡³ÊÁö ¼º´É Æò°¡ |
ÀúÀÚ¸í |
¹Ú¼ºÃ¶(Park, Seong-cheol) ; ÇÏÁÖ¿Ï(Ha, Ju-wan) ; ±èȯ¿ë(Kim, Hwan-yong) ; ¼Û¿µÇÐ(Song, Young-hak) |
¼ö·Ï»çÇ× |
Çѱ¹°ÇÃàģȯ°æ¼³ºñÇÐȸ ³í¹®Áý, Vol.12 No.6 (2018-12) |
ÆäÀÌÁö |
½ÃÀÛÆäÀÌÁö(669) ÃÑÆäÀÌÁö(11) |
ÁÖÁ¦¾î |
BEMS ; ½ÇÃøµ¥ÀÌÅÍ ; Áö¿½Ã½ºÅÛ ; Ã࿽ýºÅÛ ; ¿îÀüÇöȲ ºÐ¼® ; BEMS (BuildingEnergyManagementSystem) ; Measured Data ; Geothermal System ; Heat Storage System ; Operation Status Analysis |
¿ä¾à2 |
Energy consumption savings in buildings should be reviewed in diverse areas such as air conditioning system and lighting responsible for cooling and heating, and energy management systems such as BAS (Building Automation System) and BEMS (Building Energy Management System) are introduced to improve energy consumption efficiency and to promote economic control of related facilities by integrated management of energy generated and consumption in buildings. The measured building of this study uses regenerative geothermal system. Measured values of heat pump and system COP were 4.7 and 4.2 respectively, and they were found to be higher 11.9% and 23.5% than rated values. As a result of analyzing the air conditioning and lighting energy from the first floor to the fourth floor performing the air conditioning, the second and third floors, which have a high frequency of use, are compared with the first and fourth floors 50% higher energy consumption ratio. On the other hand, the general heat storage system uses the nighttime power of the previous day to store heat and use it the next day. The total number of days of abnormal operation during the summer season is 61 days. The electricity cost corresponding to the abnormal operation is 1,840,641 KRW, and the normal operation using the nighttime power is 1,363,561 KRW, which is difference of 477,080 KRW, 35% increase in cost. We will utilize it as the main data of BEMS through analysis of winter operation characteristics as well as summer operation characteristics. |