³í¹®¸í |
High - Performance Buildings ±¸ÇöÀ» À§ÇÑ ½Å±â¼ú °³¿ä ¹× ¿¡³ÊÁö Àý°¨ È¿°ú ºÐ¼® / Analysis of New Technologies for Energy Conservation in High - Performance Buildings / 8-D Ưº°¼¼¼Ç : Àú¿¡³ÊÁö °ÇÃà Áö¿ø½Ã½ºÅÛ 1 |
ÀúÀÚ¸í |
±èöȣ(Chul-Ho Kim) ; ¾çÀÚ°(Ja-Kang Yang) ; À̽¾ð(Seung-Eon Lee) ; À¯±âÇü(Ki-Hyung Yu) ; ±è°¼ö(Kang-Soo Kim) |
¼ö·Ï»çÇ× |
´ëÇѼ³ºñ°øÇÐȸ 2015³âµµ ÇϰèÇмú¹ßÇ¥´ëȸ (2015-06) |
ÆäÀÌÁö |
½ÃÀÛÆäÀÌÁö(673) ÃÑÆäÀÌÁö(4) |
ÁÖÁ¦¾î |
; Building materials database ; Building energy integrated support system ; Entity definition |
¿ä¾à2 |
In this study, new technologies of building and equipments to perform high - performance building was reviewed from the preceding studies. For the wall and roof insulating methods, preceding studies showed that about 19% energy were saved by improving roof insulation and applying proper outside insulation. For the windows and glazing system, preceding studies showed that Low-e glazing system could save about 8% energy compared to single glazing system. Studies about the solar and daylighting controls revealed that effective daylighting dimming control could save 11% energy compared to uncontrolled situation. Studies on DOAS showed that about 22% energy were saved compared to standard VAV system. Studies on the active chilled beam showed that about 19% energy were saved compared to standard VAV system and studies applying UFAD consumed 27% less energy than applying overhead system. |